Data Centre PUE: How to Calculate It and Reduce Energy Costs

Data Centre PUE: How to Calculate It and Reduce Energy Costs



What is power usage effectiveness (PUE)?

Power Usage Effectiveness (PUE) is the ratio of a data centre’s total energy consumption to the energy consumed by its IT equipment over the same period. It shows the additional energy needed for cooling, power distribution and other supporting infrastructure. 

For facilities and IT managers, the question is what that figure means for the budget. Is there scope to reduce cooling demand? Would changes to the existing equipment deliver enough savings to justify the cost? 

This guide explains how to calculate PUE and works through a cost example. You can also use Infiniti’s PUE calculator to check your own figures.

How do you calculate data centre PUE? 

Power Usage Effectiveness is calculated by dividing total data centre energy consumption by IT equipment energy consumption over the same reporting period:

PUE = Total facility energy (kWh) ÷ IT equipment energy (kWh)

The facility measurement includes IT consumption alongside cooling, power conversion and distribution losses, lighting and other supporting infrastructure within the defined data centre boundary.

For example, a facility consuming 1,500,000 kWh annually, of which 1,000,000 kWh supplies IT equipment: 

Annual PUE = 1,500,000 ÷ 1,000,000 = 1.50 (PUE Score)

The remaining 500,000 kWh represents infrastructure overhead which is equivalent to 50% of IT energy consumption, or approximately 33% of total facility consumption.

Measurement consistency is essential! Both readings must cover the same period, with clearly defined metering points and appropriate allocation of any shared building services. Annual energy measurements capture seasonal cooling variations and changes in operating load. Simultaneous kW readings provide a snapshot PUE estimate, which should be identified as such rather than presented as an annual PUE. ISO/IEC 30134-2:2026 sets out how to measure, calculate and report PUE, including guidance on measurement boundaries and data centres that share a building with other uses.

PUE Performance Calculator
Instantly calculate your PUE, energy costs and potential savings
0 kW
0 kW1,000 kW
Specify the total IT load in kW

(The total power used by IT equipment such as servers, storage and networking devices. This can be found on PDU displays, UPS outputs or DCIM systems)
0 kW
0 kW1,000 kW
Specify the total facility load in kW

(The total facility power including IT load and supporting systems such as cooling, UPS and lighting. Typically available from the main distribution board or BMS)
£0.27
Cost of electricity per kilowatt-hour in GBP (£)

(The cost of electricity per kilowatt hour. An average rate has been applied below, but you can adjust this to reflect your actual tariff)
Panel only seen by widget owner


What is a good PUE for a data centre? 

A lower PUE means less energy is spent on cooling and other supporting mission critical systems for each unit of energy consumed by IT equipment. A figure nearer 1.0 is better in that respect, although a realistic target depends on the building, local climate, IT load and resilience requirements. 

For an older server room, a hyperscale facility’s published PUE may not be a useful benchmark. Your own operating records can offer a more relevant comparison. When reviewing readings before and after an upgrade, check whether the IT load or weather conditions have changed too. Keep the same metering boundaries so that you’re comparing equivalent figures. 

PUE alone won’t tell you whether your servers are making efficient use of electricity. You could improve the ratio while total consumption rises. Review it alongside electricity use and IT utilisation, and include water consumption and carbon emissions when assessing the facility’s wider environmental performance.

How much could reducing PUE save?

Consider a data centre with a constant IT load of 100 kW. Reducing its annual PUE from 1.8 to 1.5 would change its average total power demand as follows:

Measure               
    
Before Improvement

After Improvement

Annual PUE
1.81.5
Average total facility demand
180 kW150 kW

With the facility running around the clock, a 30 kW reduction adds up to 262,800 kWh over a year. 

Annual energy saving: 30 kW × 8,760 hours = 262,800 kWh 

Using 25p per kWh as an example rate, that’s £65,700 less spent on electricity over the year. 

This example assumes an unchanged IT load and electricity tariff. Actual savings depend on site conditions, and any investment decision should include installation costs and ongoing maintenance.

How can you improve your data centre's PUE? 

Start with measurements you can trust, then take a closer look at how the infrastructure is running.

Check for gaps around cabinets where cooled air can bypass equipment, and look for hot exhaust air finding its way back to server inlets. Do the cooling settings match demand? It’s also worth checking how heavily the power systems are loaded and where losses occur. 

For a closer look at cooling improvements, read our guide to data centre cooling optimisation, which covers reducing energy use without compromising uptime.

Before making changes, check that the data centre will still have the cooling capacity and backup power it needs during a fault or maintenance. Weigh the expected energy savings against those requirements.


Contact us today on 0844 225 0094 t
o book an exploratory meeting or click below to fill in our contact request form:

Discover what our data centre consultancy services can offer.

Please enter the 4 digit security code, shown below:

wcs image 1wcs image 2wcs image 3wcs image 4



Frequently asked questions about data centre PUE

What does PUE mean in a data centre?

PUE (Power Usage Effectiveness) measures how much energy a data centre uses overall for each unit of energy consumed by its IT equipment. It accounts for the additional energy needed to run cooling, power distribution and other supporting systems. A lower PUE indicates less energy is required to support the IT load..

How do you calculate data centre PUE?

Divide total data centre energy consumption by IT equipment energy consumption over the same period:

PUE = total data centre energy ÷ IT equipment energy

For example, a data centre using 150,000 kWh in total, with 100,000 kWh consumed by IT equipment, has a PUE of 1.5.

What does a PUE of 1.5 mean?

A PUE of 1.5 means the data centre uses 1.5 kWh of total energy for every 1 kWh used by IT equipment. The remaining 0.5 kWh supports cooling, power delivery and other infrastructure. 

In this example, supporting systems account for approximately one-third of total energy consumption.

Can I calculate PUE using power readings?

Power readings taken at the same time can provide an estimate of PUE at that moment. For an annual figure, divide the data centre’s total energy consumption by the energy used by its IT equipment, using kWh readings covering the same full year.

Does PUE include cooling and UPS losses?

Yes. PUE includes the energy used by IT equipment alongside cooling and other supporting systems, including losses through UPS units and power distribution.

Excluding any of these loads can produce an artificially low PUE, making the data centre appear more efficient than it is. Consistent measurement boundaries help ensure that changes in PUE reflect actual changes in performance.

Does a lower PUE mean a data centre is more sustainable?

A lower PUE means less energy is used by supporting systems relative to the IT equipment. However, it does not tell you how much carbon the data centre emits, how much water it uses or how effectively its servers handle workloads. For a fuller picture, consider PUE alongside overall energy use, the electricity supply, water consumption and IT utilisation.